BOSCH REXROTH
R901077297
- BOSCH REXROTH
- Material:R901077297
- Model:VT-VSPD-1-2X/V0/0-0-1
Due to extremely high demand, please call 877-366-7226 for availability
The Bosch Rexroth VT-VSPD-1-2X/V0/0-0-1 (R901077297) is a sophisticated valve amplifier designed to enhance the precision and control of hydraulic systems. This amplifier is a versatile component that comes as a printed circuit board in the European format, equipped with a microcontroller at its core to manage the entire operational process. The device boasts nonvolatile flash memory storage for configuration data, command values, and up to 10 parameter sets. With four binary-coded digital inputs, users can select and activate command values for valve spool positions along with associated ramp times. The amplifier also features additional control inputs for enabling command value validity and acknowledging fault messages. Users can preset command values through digital call-ups or via analog inputs, accommodating voltage presets of 0 to 10 V or current presets ranging from 4 to 20 mA. The unit allows for precise control over solenoids A and B using variable command values, with digital commands being additive to analog ones based on the selected parameter set. Software customization of signal levels is possible for both command value inputs and ramp generation. Externally adjustable ramps are achievable through analog inputs AI1+/- and AI2+/-. Additionally, the amplifier includes a step function generator for managing overlap jumps in overlapped control spools. Activation control and error messaging are straightforward; an H level at the enable input activates control while error logic detects issues such as cable breaks or inactive enable inputs. Parameterization and diagnostics are conducted via a serial interface or directly on the display version without a PC. The device supports up to 10 valve amplifiers connected via a local bus, each assigned a unique address through BODAC software. With its comprehensive features including selectable valve controls, programmable output stages, ramp generators, digital input parameters call-up, fault outputs, and configurable measuring sockets, this valve amplifier is an integral component for achieving refined hydraulic system management.
The valve amplifier is set-up as printed circuit board in Europe format 100 mm x 160 mm with daughter board, fitted on both sides.
The central unit of the amplifier is a microcontroller which controls the entire process. Data for configuration, command values and parameters are stored in a FLASH in a non-volatile form.
Four binarily coded digital inputs are used to call up parameter sets (command values) from the memory in which you can store a maximum of 16 sets. A call-up activates the command value for the valve spool position with the related ramp times.
More control inputs have the following functions:
Command value valid:
enable by the parameter set activated by the current call-up (H active)
Enable:
activation of the outputs (acknowledge fault message with low→high edge)
The command value can be preset via digital command value call-ups [5] and/or via analog inputs [1]. The analog input AI4 (b14/b16) is to be used for the command value presetting of ±10 V, the analog input AI6 (b22/b24) for any command value presetting from 4 to 20 mA.
Command values from 0 to +10 V (12...20 mA) control solenoid B.
Command values from 0 to –10 V (4...12 mA) control solenoid A.
The digital command value is added to the analog command value with the correct sign, according to the set call-up.
The command value inputs can be varied by means of software in the signal level.
Apart from the internal ramp generation option, you can also influence the ramp for “up” and “down” from external signals with correct total and correct sign by means of the AI2 (b6/b8) and AI5 (b18/b20) analog inputs.
For the valves, the software configures a step function generator [8] for the realization of the overlap jump if an overlapped control spool is selected.
Enable and error messages
The control is activated by the H level at the enable input. If no command value call-up is active, the digital call-up 0 is set.
Error logics [13] identify any cable break of the command value input for 4 to 20 mA as well as an inactive enable input. If there is an error, a fault message is output to (d22) by means of a low signal and displayed visually by the “OK” LED (LED goes out) on the front plate. It is possible to configure the enable so that an inactive enable input is not displayed as error.
Parameterization and diagnosis
Selection of the valve to be controlled and selection and configuration of the command value input, the ramp generator and the enable input as well as the setting of the command value call-up parameters are effected via the serial interface [17] at the front-side D-Sub socket. Via the local bus [16], up to 32 valve amplifiers can be connected. Via BODAC, every valve amplifier is assigned a bus address. Reconnection of the serial interface cable is not required. Additional information in the instructions 30523-01-B.
In the version with display, configuration, parameterization and diagnosis are possible without PC, directly at the display.
[ ] = Assignment to the block diagram
|
01 |
Valve amplifiers for proportional valves without electrical position feedback, digital, Euro-card format |
VT-VSPD |
|
02 |
For valves: |
1 |
|
03 |
Component series 20 ... 29 (20 ... 29: unchanged technical data and pin assignment) |
2X |
|
04 |
Version: standard |
V0 |
|
05 |
Without display |
0 |
|
With display |
1 |
|
|
06 |
Option: standard |
0 |
|
07 |
With valve output stage |
1 |
|
01 |
02 |
03 |
04 |
05 |
06 |
07 |
||||||
|
VT-VSPD |
‒ |
1 |
‒ |
2X |
/ |
V0 |
/ |
‒ |
0 |
‒ |
1 |
General
|
Component series |
2X | |
|
Type of electronics |
Digital | |
|
Design |
Euro-card |
Voltage supply
|
Operating voltage |
nominal |
U |
V |
24 |
|
Lower limit value |
UB(t)min |
V |
21 | |
|
Upper limit value |
UB(t)max |
V |
30 | |
|
Current consumption |
max. |
Imax |
A |
1.5 |
|
Standby current |
A |
270 | ||
|
Fuse |
4 A time-lag | |||
Analog inputs
|
Command value |
Voltage inputs |
Number and designation |
3 (AI2, AI4, AI5) | ||
|
Voltage (differential input) |
U |
V |
0 ... ±10 | ||
|
Input resistance |
R |
kΩ |
≥ 100 | ||
|
Voltage |
Input resistance |
AI2 |
R |
MΩ |
10 |
|
Resolution for ± 10 |
mV |
5 | |||
|
Resolution for 0...10 |
mV |
2.5 | |||
|
Non-linearity |
mV |
< 10 | |||
|
Current |
Command value |
I |
mA |
4 … 20 | |
|
Input resistance |
R |
Ω |
100 | ||
|
Resolution |
μA |
5 | |||
|
Leakage current |
0.15 (with 500 Ω between pin b24, b8, b20 and 0 V) | ||||
|
Parameter sets |
Quantity |
callable command values |
16 | ||
Digital inputs
|
Digital inputs |
Number and designation |
4/16 | ||
|
Signal |
log 0 |
0 ... 5 | ||
|
log 1 |
16 ... UB | |||
Analog outputs
|
Voltage |
kV |
0 … ±10 | |
|
Load resistance |
1 | ||
|
Resolution |
1.25 (14 bit) | ||
|
Residual ripple |
±15 (without noise) |
Digital outputs
|
Digital outputs |
Signal |
log 1 1) |
UB - 3V | |
|
log 0 |
0 ... 5 |
| 1) | Imax = 30 mA, short-circuit-proof |
Solenoid outputs
|
Solenoid current |
max. |
Imax |
A |
2.5 |
|
Solenoid resistance |
max. |
Ω |
19 |
Adjustment options
|
Ramp time up/down |
Ramp 1 |
t |
s |
0 … 300 |
Displays
|
LED display |
Green |
Ready for operation | |
|
yellow |
Enable |
Supplementary information
|
Reference voltage |
Potentiometer supply |
U |
V |
±10 (Imax = 30 mA, short-circuit-proof) |
|
Residual ripple |
mV |
< 20 | ||
|
Scanning time |
Command value preparation |
ms |
2 | |
|
Serial interface |
RS 232, D-Sub socket | |||
|
Local bus |
Distance to the furthermost device |
32/maximum 280 m line length | ||
|
Anschlussart |
64-pin male connector, DIN 41612, form G | |||
|
Ambient temperature range |
ϑ |
°C |
0 … 50 | |
|
Storage temperature range |
ϑ |
°C |
-20 … 70 | |
|
Weight |
m |
kg |
0.2 | |
For applications outside these parameters, please consult us!
Notice:
For information on the environment simulation testing for the areas EMC (electromagnetic compatibility), climate and mechanical load, see data sheet 30523-U.
|
1 |
U/U or I/U transformer |
|
2 |
Analog input adjustment |
|
3 |
Switching matrix |
|
4 |
Command value generation |
|
5 |
Binary command value call-ups |
|
6 |
Control of the binary call-ups |
|
7 |
Characteristic curve adjustment |
|
8 |
Step function generator |
|
9 |
Offset |
|
10 |
Amplitude limiter |
|
11 |
Measuring sockets |
|
12 |
Digital outputs |
|
13 |
Error logics |
|
15 |
Port for valve with one solenoid |
|
16 |
Local bus |
|
17 |
Serial interface |
|
X1, X2, ⊥ |
See Operating and display elements |
Pin assignment of the RS 232 socket
Pin assignment of the male multipoint connector
|
Row d |
Row b |
|||||
|
Pin |
Signal |
Description |
Pin |
Signal |
Description |
|
|
2 |
DI1 |
Binary command value call-up 1 |
2 |
n. c. |
not assigned |
|
|
4 |
DI2 |
Binary command value call-up 2 |
4 |
n. c. |
not assigned |
|
|
6 |
DI3 |
Binary command value call-up 4 |
6 |
AI2+ |
Ramp+ (U/I)+ |
|
|
8 |
DI4 |
Binary command value call-up 8 |
8 |
AI2- |
Ramp+ (U/I)- |
|
|
10 |
DI5 |
not assigned |
10 |
n. c. |
not assigned |
|
|
12 |
DI6 |
Command value valid |
12 |
n. c. |
not assigned |
|
|
14 |
DI7 |
not assigned |
14 |
AI4+ |
Command value (U)+ |
|
|
16 |
DI8 |
not assigned |
16 |
AI4- |
Command value (U)- |
|
|
18 |
DI9 |
Enable |
18 |
AI5+ |
Ramp- (U/I)+ |
|
|
20 |
DO1 |
Solenoid A active |
20 |
AI5- |
Ramp- (U/I)- |
|
|
22 |
OK |
OK output |
22 |
AI6+ |
Command value (I)+ |
|
|
24 |
Data+ |
Local bus |
24 |
AI6- |
Command value (I)- |
|
|
26 |
DO2 |
Solenoid B active |
26 |
AO3 |
Solenoid current (±10 V) |
|
|
28 |
Data- |
Local bus |
28 |
AGND |
Analog GND |
|
|
30 |
AO1 |
Valve position command value |
30 |
REF- |
-10 V |
|
|
32 |
n. c. |
not assigned |
32 |
REF+ |
+10 V |
|
|
Row z |
Row f |
|||||
|
Pin |
Signal |
Description |
Pin |
Signal |
Description |
|
|
2 |
MA+ |
Solenoid A+ 1) |
2 |
DO7 |
not assigned |
|
|
4 |
MA- |
Solenoid A- 1) |
4 |
n. c. |
not assigned |
|
|
6 |
MB+ |
Solenoid B+ |
6 |
n. c. |
not assigned |
|
|
8 |
MB- |
Solenoid B- |
8 |
n. c. |
not assigned |
|
|
10 |
Shield |
Shield |
10 |
n. c. |
not assigned |
|
|
12 |
n. c. |
not assigned |
12 |
n. c. |
not assigned |
|
|
14 |
n. c. |
not assigned |
14 |
n. c. |
not assigned |
|
|
16 |
n. c. |
not assigned |
16 |
n. c. |
not assigned |
|
|
18 |
n. c. |
not assigned |
18 |
n. c. |
not assigned |
|
|
20 |
System earth |
System earth |
20 |
n. c. |
not assigned |
|
|
22 |
DO3 |
Freely configurable |
22 |
n. c. |
not assigned |
|
|
24 |
DO4 |
Freely configurable |
24 |
n. c. |
not assigned |
|
|
26 |
DO5 |
Freely configurable |
26 |
n. c. |
not assigned |
|
|
28 |
DO6 |
Freely configurable |
28 |
n. c. |
not assigned |
|
|
30 |
UB |
Operating voltage |
30 |
n. c. |
not assigned |
|
|
32 |
L0 |
Ground 0 V |
32 |
n. c. |
not assigned |
|
|
1) Port for valve with one solenoid |
||||||
Schematic diagram
Dimensions in mm
Dimensions in mm
The amplifier card may only be unplugged and plugged when de-energized.
No connectors with free-wheeling diodes or LED displays must be used for solenoid connection.
Only carry out measurements at the card using instruments Ri > 100 kΩ.
For switching command values, relays with gold-plated contacts have to be used (low voltages, low currents).
Always shield command value lines and lead them separately; connect shielding to connection z10 on the card-side, other side open (danger of ground loops).
For solenoid conductors up to 50 m in length, use the line type LiYCY 1.5 mm2. For greater lengths, please contact us. Shield the solenoid conductors.
Use highly flexible Cu conductors (at least 2.5 mm2) to connect the system earth.
The system earth is a main part of the EMC protection of the amplifier card. It is intended to eliminate interferences which are transported via the data and supply lines. However, this is only possible if the system earth itself does not introduce interferences into the command value card.
The distance to aerial lines, radios, and radar systems has to be at least 1 m.
Do not lay solenoid conductors and signal lines near power lines.
The charging power of the smoothing capacitor on the card requires the pre-fuses to be of a slow-blowing characteristic.
Notice:
If a differential input is used, both inputs must always be connected or disconnected simultaneously.