***Disclaimer: The following summary contains information gathered from various sources such as product descriptions, technical specifications and catalogs. While efforts have been made to provide accurate details, inaccuracies may occur. It is advised to verify all information by contacting Bosch Rexroth directly.***
The Bosch Rexroth VT-VPCD-1-1X/V0/1-P-1 (R901089559) is a state-of-the-art control electronics module designed for precise adjustment of axial piston pumps, particularly the AVS type with HS control. This module is integral in managing the swivel angle and pressure control, as well as power limitation, through an electrically controlled proportional valve. It uses advanced feedback systems including an inductive position transducer for swash plate positioning and a pressure transducer for accurate pressure measurement. The VT-VPCD-1-1X/V0/1-P-1 ensures dynamic performance by calculating the actual power value from the swivel angle and pressure data, with software ensuring that the most appropriate controller is active according to the working point. In its default state, the valve control spool maintains a central position until there's a demand from superior controllers to adjust flow or pressure. This module's control electronics are built on a double-sided printed circuit board featuring a microcontroller at its core, which orchestrates the entire process and executes controller functions. It stores configuration data and command values in non-volatile FLASH memory. Up to 16 parameter sets can be stored and easily accessed through binary-coded digital inputs. For precise control inputs, it includes differential inputs for analog command value presetting alongside digital call-up command values. The output stage is regulated based on these inputs to ensure optimal performance of the axial piston pump. The VT-VPCD-1-1X/V0/1-P-1 also offers modes for pressure control that can work with either one or two pressure sensors, catering to both open and closed circuit applications. Moreover, it features diagnostic capabilities that identify faults such as cable breaks or short circuits in sensor readings or deviations in control loops. Errors are indicated via output signals and can be displayed for quick troubleshooting. Parameterization and diagnosis are facilitated through a serial interface that allows configuration of pump size, leakage oil correction, sequence control activation/deactivation, switching outputs, test outputs via BODAC software. It also supports masterslave functionality and mooring capability with optional PROFIBUS connectivity. Overall, this Bosch Rexroth electronic module represents an advanced solution for controlling variable displacement axial piston pumps within various hydraulic systems requiring precise motion control and power management.

Functional description using the A4VS axial piston pump with HS4 control as example

The swivel angle and pressure control as well as the power limitation of the A4VS… variable displacement pump are realized by an electrically controlled proportional valve (1). Via the actuating piston (2) of the pump, this valve determines the position of the swash plate (3).

If the pump does not rotate, in case of depressurized high pressure and actuating system and if enable is not operated, the swash plate is held in the "Zero" swivel angle position by the spring centering.

The position of the swash plate is determined by an inductive position transducer (4), the actual pressure value is recorded by a pressure transducer. Both actual values are supplied to the VT-VPCD control electronics and linked with each other by the software.

The actual power value is calculated from the product of actual pressure value and actual swivel angle value. The controller software ensures by means of a minimum value generator that the controller corresponding to the working point is always active.

In the static condition (i.e. swivel angle command value equals actual swivel angle value, power command value equals actual power value or pressure command value equals actual pressure value) the valve control spool is in central position.

If the superior controllers demand e.g. an increase in the swivel angle (corresponds to an increase in the flow), the valve control spool must be deflected out of the central position until the swivel angle has reached the required value.

The sectional drawing shows the A4VS… variable displacement pump with HS4 control; the proportional valve (1) is controlled using the VT-VPCD control electronics.

Notice for the HS4 control:

With de-energized proportional valve and pump with clockwise rotation and if the set pressure is available, the pump swivels to swivel angle α = 0 (A4VSO design) or α = –100 % (A4VSG design).

technical illustration-R901089559-Control electronics for adjustment of axial piston pumps A4VS…HS4 (NG40 to NG1000) and A2V…EO4 (NG500 to NG1000) Pressure controller with subordinate swivel angle controller Parameterizable power limitation Leakage compensation Master/slave capability Mooring capability PROFIBUS (optional)

Functional description of the control electronics

The control electronics is set-up as printed circuit board, fitted on both sides. It comprises a switching power supply unit [1] creating all internally required voltages.

The central unit is a microcontroller controlling the entire process and realizing the controller functions. Data for configuration, command values and parameters are stored in a FLASH in a non-volatile form.

Four binarily coded digital inputs are used to call up parameter sets (command values) from the memory in which you can store a maximum of 16 sets. A call-up activates a command value for the swivel angle, the pressure and the power limitation as well as ramp times for swivel angle and pressure.

More control inputs have the following functions:

"Command value valid":
Enabling of the parameter set addressed by the current call-up (H active)

"Enable":
Activation of the control (H active)

Please note:

H active = activate at high level

Via the differential inputs AI7, AI5 and AI4 [3], the analog command value presetting for the swivel angle, the pressure and the maximum power are specified. With a positive swivel angle command value, the pump swivels in "counterclockwise" swivel direction (= direction of flow P → B). The digital call-up command values are added to the analog command values; the total of both command values is supplied to the controller input via the relevant ramp generators.

The controller output signal controls the output stage [6] depending on the command/actual value differences.

The position of the valve control spool [11], the swivel angle of the variable displacement pump [12a, 12b or 12c] and the system pressure [13] are measured and supplied to the control loop via evaluation electronics [7].

Modes for pressure control

Depending on the configuration, the pressure controller works with one or two pressure sensors.

Open circuit:
1 sensor, optionally current or voltage

Closed circuit:
2 sensors, optionally current or voltage

In the closed circuit, both pressure sensors are evaluated. As soon as the control electronics is in pressure control, the larger of the two pressures determines the control behavior. To compensate control deviations (pressure command value - actual pressure value), the pressure controller can also swivel the pump to the opposite side as well as beyond its specified swivel angle command value.

The switching outputs are configured via BODAC. The following functions may be selected:

DO1: Swivel angle control active

DO2: Pressure control active

DO3: Power limitation active

DO4 Slave mode active

DO5: Swivel angle in the accuracy window

DO6: Pressure in the accuracy window

DO7: Rectangular 32 Hz

The test output (b26 or measuring socket X1) is also configured via BODAC. It is used for the analog output of internal variables.

Enable and error messages

Setting the enable input activates the control. If no command value call-up is activated, parameter set 0 is set.

Error logics identify the following faults:

Cable break or short-circuit in the actual valve value recording

Cable break or short-circuit in actual swivel angle value acquisition

Cable break at the pressure transducer (only current interface)

Closed-loop errors (i.e. control deviations between swivel angle command value and actual swivel angle value)

An error is indicated at output d22. The "OK" message goes out, signal level is 0 V.

Errors are also shown at the display.

Parameterization and diagnosis

Using the serial interface [2], the pump size is selected and the leakage oil correction and the sequence control are activated or deactivated and switching outputs and the test output are configured via BODAC at the front-side D-Sub socket. Via the local bus, up to 32 control electronics can be connected. Via BODAC, every control electronics is assigned a bus address. Reconnection of the serial interface cable is not required. More information in document 30028-01-B.

[ ] = Assignment to the block diagrams

 

VT-VPCD control electronics in connection with the axial piston pump A4VS…HS4 or A2V…EO4 serves for realization of all electrical functions required for adjustment. Parameterization is effected via a serial interface.

 

01

Digital control electronics for controlling axial piston variable displacement pumps

VT-VPCD-1

02

Component series 10 ... 19 (10 ... 19: unchanged installation and connection dimensions)

1X

03

For axial piston pump A4VS…HS4 with swivel angle sensor AWX F004 D01 and for axial piston pump A2V…EO4 (housing pump) with swivel angle sensor MCP-40/4742

V0

For axial piston pump A2V...EO4 (installation pump) with swivel angle sensor DK 100 (only available bus connection)

V100

04

With display

1

05

Without bus connection

0

PROFIBUS DPV0

P

DeviceNet

D

CANopen

C

06

With valve output stage

1

01

02

03

04

05

06

VT-VPCD-1

‒

1X

/

/

1

‒

‒

1

General

Component series

1X

Type of electronics

Digital

Design

Euro-card format

Voltage supply

Operating voltage

nominal

U

V

24

Lower limit value

UB(t)min

V

21

Upper limit value

UB(t)max

V

30

Current consumption

max.

Imax

A

3.5

Analog inputs

Voltage

Number and designation

7 (AI1 ... AI7)

Command value

Voltage

Differential input 1

U

V

​0 ... ±10

Differential input 2

U

V

​0 … +10

Input resistance

R

kΩ

100

Voltage

Resolution for 0...10

U

mV

5

Resolution for ± 10

U

mV

2.5

Non-linearity

U

mV

10

Current

Number and designation

4 (AI2, AI4, AI5, AI6)

Command value

Current

I

mA

4 … 20

Input resistance 1)

R

Ω

100

Current

Resolution

I

μA

5

Leakage current

I

0.15 (with 500 Ω between port AI x - and 0 V)
1) Voltage drop at actual pressure value input with 4 mA approx. 1.7 V, with 20 mA approx. 3.5 V

Digital inputs

Signal

log 0

V

0 ... 5

log 1

V

16 ... UB

Analog outputs

Voltage

Number and designation

U

3 (AO1, AO2, AO3)

U

V

​0 … ±10

Load resistance

U

1 kΩ

Resolution

U

10 (11 bit)

Residual ripple

U

±25 (without noise)

Digital outputs

Signal

log 1 1)

V

UB - 3V

log 0

V

0 ... 5
1) Imax = 30 mA, short-circuit-proof

Solenoid outputs

Solenoid current

max.

Imax

A

2.5

Coil resistance at 20°C

R

Ω

2.7

Position transducer

Oscillator voltage

U

V

10

Oscillator frequency

f

kHz

5

Other information

Reference voltage

Potentiometer supply

U

±10 (Imax = 30 mA)

Residual ripple

U

mVpp

20

Scanning time

Command value preparation

T

ms

2

Serial interface

RS 232, D-Sub socket

Local bus

Distance to the furthermost device

I

32/maximum 280 m line length

Anschlussart

64-pin male connector, DIN 41612, form G

Ambient temperature range

ϑ

°C

​0 … ​50

Storage temperature range

ϑ

°C

-20 … ​70

Weight

m

kg

0.2

Peripherals, system information

Current consumption per solenoid

max.

Imax

A

2.5

Regulated solenoid current

at constant swivel angle

I

Solenoid a: 450 mA, solenoid b: 700 mA

Solenoid coil resistance

Cold value at 20 °C

R

Ω

2.7

at maximum hot value

R

Ω

4.05

Position transducer carrier frequency

f

kHz

5

Position transducer coil resistance

at 20 °C port 1 + 2

R

Ω

150 ± 11 Ω

at 20 °C port 3 + 4

R

Ω

50 ± 3,5 Ω

Hysteresis

%

≤ 0.2

Repetition accuracy

%

≤ 0.2

linearity deviation

Swivel angle

%

≤ 1

Pressure

%

≤ 1.5 of the maximum measuring pressure of the pressure transducer

Notice:

For information on the environment simulation testing for the areas EMC (electro-magnetic compatibility), climate and mechanical load, see data sheet 30028-U.

For applications outside these parameters, please consult us!

technical illustration-R901089559-Control electronics for adjustment of axial piston pumps A4VS…HS4 (NG40 to NG1000) and A2V…EO4 (NG500 to NG1000) Pressure controller with subordinate swivel angle controller Parameterizable power limitation Leakage compensation Master/slave capability Mooring capability PROFIBUS (optional)

LED displays

Enable activated

OK

Ready for operation

±

Sign display for 4-digit indicator

4-digit alphanumerical display

Indicator for configuration, parameterization and diagnosis

I1 … I4

Binary command value call-ups

I5

Slave mode

I6

Command value valid

I7 … I8

not assigned

O1

Swivel angle control enabled

O2

Pressure control enabled

O3

Power limitation active

O4

Slave mode active

O5

Swivel angle in the accuracy window

O6

Pressure in the accuracy window

O7

Rectangular signal 32 Hz

Measuring sockets

X1

Process signal (selection via BODAC)

X2

Process signal (selection via BODAC)

⊥

Reference potential

VT-VPCD-1-1X/V0/1-0-1 for A4VS...HS4 axial piston pump with AWX F004 D01 swivel angle sensor

technical illustration-R901089559-Control electronics for adjustment of axial piston pumps A4VS…HS4 (NG40 to NG1000) and A2V…EO4 (NG500 to NG1000) Pressure controller with subordinate swivel angle controller Parameterizable power limitation Leakage compensation Master/slave capability Mooring capability PROFIBUS (optional)

VT-VPCD-1-1X/V0/1-0-1 for A4VS...HS4 axial piston pump with AWX F004 D01 swivel angle sensor

1

Power supply unit

2a

Serial interface

2b

PROFIBUS interface, optional

2c

CAN bus interface, optional

2d

Local bus

3

Voltage or current input

4

Level converter

5

Microcontroller

6

Power output stage

7

Oscillator/demodulator

8

Voltage output

9

Output driver

10

Proportional valve

11

Position transducer of valve

12a

Swivel angle sensor of pump

13a

Pressure transducer (open circuit)

13b

Pressure transducer (closed circuit)

VT-VPCD-1-1X/V0/1-0-1 for axial piston pump A2V…EO4 (housing pump) with swivel angle sensor MCP-40/4742

technical illustration-R901089559-Control electronics for adjustment of axial piston pumps A4VS…HS4 (NG40 to NG1000) and A2V…EO4 (NG500 to NG1000) Pressure controller with subordinate swivel angle controller Parameterizable power limitation Leakage compensation Master/slave capability Mooring capability PROFIBUS (optional)

VT-VPCD-1-1X/V0/1-0-1 for A4VS...HS4 axial piston pump with AWX F004 D01 swivel angle sensor

1

Power supply unit

2a

Serial interface

2b

PROFIBUS interface, optional

2c

CAN bus interface, optional

2d

Local bus

3

Voltage or current input

4

Level converter

5

Microcontroller

6

Power output stage

7

Oscillator/demodulator

8

Voltage output

9

Output driver

10

Proportional valve

11

Position transducer of valve

12a

Swivel angle sensor of pump

13a

Pressure transducer (open circuit)

13b

Pressure transducer (closed circuit)

VT-VPCD-1-1X/V100/1-0-1 for axial piston pump A2V…EO4 (installation pump) with swivel angle sensor DK 100

technical illustration-R901089559-Control electronics for adjustment of axial piston pumps A4VS…HS4 (NG40 to NG1000) and A2V…EO4 (NG500 to NG1000) Pressure controller with subordinate swivel angle controller Parameterizable power limitation Leakage compensation Master/slave capability Mooring capability PROFIBUS (optional)

1

Power supply unit

2a

Serial interface

2b

Local bus

3

Voltage or current input

4

Level converter

5

Microcontroller

6

Power output stage

7

Oscillator/demodulator

8

Voltage output

9

Output driver

10

Proportional valve

11

Position transducer of valve

12c

Swivel angle sensor of pump

13a

Pressure transducer (open circuit)

13b

Pressure transducer (closed circuit)

Pin assignment of the male multipoint connector
VT-VPCD-1-1X/V0/1-0-1 for A4VS...HS4 axial piston pump with AWX F004 D01 swivel angle sensor

Row d

Row b

Pin

Signal

Description

Pin

Signal

Description

2

DI1

Binary command value call-up 1

2

AI3+

Slave swivel angle command value (in case of slave operation)

4

DI2

Binary command value call-up 2

4

AI3-

Slave swivel angle command value, reference

6

DI3

Binary command value call-up 4

6

AI2+

Actual pressure value pA, (I or U)

8

DI4

Binary command value call-up 8

8

AI2-

Actual pressure value pA, reference

10

DI5

Slave mode

10

n. c.

not assigned

12

DI6

Command value valid

12

n. c.

not assigned

14

n. c.

not assigned

14

AI4+

Swivel angle command value

16

n. c.

not assigned

16

AI4-

Swivel angle command value, reference

18

DI9

Enable

18

AI5+

Pressure command value

20

DO1

Swivel angle control enabled

20

AI5-

Pressure command value, reference

22

OK

OK output

22

AI6+

Actual pressure value pB, (I or U)

24

Data+

Local bus

24

AI6-

Actual pressure value pB, reference

26

DO2

Pressure control enabled

26

AO3

Test output (measuring socket X1)

28

Data-

Local bus

28

AGND

Analog GND

30

AO1

Control of valve with OBE

30

REF-

-10 V

32

AO2

Resulting swivel angle command value for master/slave operation

32

REF+

+10 V

Row z

Row f

Pin

Signal

Description

Pin

Signal

Description

2

MA+

Solenoid A+

2

DO7

Rectangular signal 32 Hz

4

MA-

Solenoid A-

4

n. c.

not assigned

6

MB+

Solenoid B+

6

n. c.

not assigned

8

MB-

Solenoid B-

8

AI7+

Power command value

10

Shield

Shield

10

AI7-

Power command value, reference

12

L1O-

Position transducer of valve, feed -, pin 2

12

n. c.

not assigned

14

L1I-

Position transducer of valve, actual value –, pin 4

14

n. c.

not assigned

16

L1I+

Position transducer of valve, actual value +, pin 3

16

n. c.

not assigned

18

L1O+

Position transducer of valve, feed +, pin 1

18

n. c.

not assigned

20

System earth

System earth

20

L2O-

Swivel angle sensor of pump, feed –, pin 2

22

DO3

Power limitation active

22

L2I-

Swivel angle sensor of pump, actual value –, pin 4

24

DO4

Slave mode active

24

L2I+

Swivel angle sensor of pump, actual value +, pin 3

26

DO5

|αcommand – αactual| < window

26

L2O+

Swivel angle sensor of pump, feed +, pin 1

28

DO6

|pcommand – pactual| < window

28

CAN Gnd

CAN bus reference

30

UB

Operating voltage

30

CAN L

CAN bus input/output

32

L0

Ground 0 V

32

CAN H

CAN bus input/output

Pin assignment of the male multipoint connector
VT-VPCD-1-1X/V0/1-0-1 for A2V...EO4 axial piston pump (housing pump) with MCP-40/4742 swivel angle sensor

Row d

Row b

Pin

Signal

Description

Pin

Signal

Description

2

DI1

Binary command value call-up 1

2

AI3+

Slave swivel angle command value (in case of slave operation)

4

DI2

Binary command value call-up 2

4

AI3-

Slave swivel angle command value, reference

6

DI3

Binary command value call-up 4

6

AI2+

Actual pressure value pA, (I or U)

8

DI4

Binary command value call-up 8

8

AI2-

Actual pressure value pA, reference

10

DI5

Slave mode active

10

AI1+

Swivel angle sensor of pump, pin 2

12

DI6

Command value valid

12

AI1-

Swivel angle sensor of pump, pin 5

14

n. c.

not assigned

14

AI4+

Swivel angle command value

16

n. c.

not assigned

16

AI4-

Swivel angle command value, reference

18

DI9

Enable

18

AI5+

Pressure command value

20

DO1

Swivel angle control enabled

20

AI5-

Pressure command value, reference

22

OK

OK output

22

AI6+

Actual pressure value pB, (I or U)

24

Data+

Local bus

24

AI6-

Actual pressure value pB, reference

26

DO2

Pressure control enabled

26

AO3

Test output (measuring socket X1)

28

Data-

Local bus

28

AGND

Analog GND / Swivel angle sensor of pump, pin 5

30

AO1

Control of valve with OBE

30

REF-

-10 V

32

AO2

Resulting swivel angle command value for master/slave operation

32

REF+

+10 V / swivel angle sensor of pump, pin 4

Row z

Row f

Pin

Signal

Description

Pin

Signal

Description

2

MA+

Solenoid A+

2

DO7

Rectangular signal 32 Hz

4

MA-

Solenoid A-

4

n. c.

not assigned

6

MB+

Solenoid B+

6

n. c.

not assigned

8

MB-

Solenoid B-

8

AI7+

Power command value

10

Shield

Shield

10

AI7-

Power command value, reference

12

L1O-

Position transducer of valve, feed -, pin 2

12

n. c.

not assigned

14

L1I-

Position transducer of valve, actual value –, pin 4

14

n. c.

not assigned

16

L1I+

Position transducer of valve, actual value +, pin 3

16

n. c.

not assigned

18

L1O+

Position transducer of valve, feed +, pin 1

18

n. c.

not assigned

20

System earth

System earth

20

n. c.

not assigned

22

DO3

Power limitation active

22

n. c.

not assigned

24

DO4

Slave mode active

24

n. c.

not assigned

26

DO5

|αcommand – αactual| < window

26

n. c.

not assigned

28

DO6

|pcommand – pactual| < window

28

CAN Gnd

CAN bus reference

30

UB

Operating voltage

30

CAN L

CAN bus input/output

32

L0

Ground 0 V

32

CAN H

CAN bus input/output

Pin assignment of the male multipoint connector
VT-VPCD-1-1X/V100/1-0-1 for A2V...EO4 axial piston pump (installation pump) with DK 100 swivel angle sensor

Row d

Row b

Pin

Signal

Description

Pin

Signal

Description

2

DI1

Binary command value call-up 1

2

AI3+

Slave swivel angle command value (in case of slave operation)

4

DI2

Binary command value call-up 2

4

AI3-

Slave swivel angle command value, reference

6

DI3

Binary command value call-up 4

6

n. c.

not assigned

8

DI4

Binary command value call-up 8

8

n. c.

not assigned

10

DI5

Slave mode active

10

n. c.

not assigned

12

DI6

Command value valid

12

n. c.

not assigned

14

n. c.

not assigned

14

AI4+

Swivel angle command value

16

n. c.

not assigned

16

AI4-

Swivel angle command value, reference

18

DI9

Enable

18

AI5+

Pressure command value

20

DO1

Swivel angle control enabled

20

AI5-

Pressure command value, reference

22

OK

OK output

22

AI6+

Actual pressure value pB, (I or U)

24

Data+

Local bus

24

AI6-

Actual pressure value pB, reference

26

DO2

Pressure control enabled

26

AO3

Test output (measuring socket X1)

28

Data-

Local bus

28

AGND

Analog GND

30

AO1

Control of valve with OBE

30

REF-

-10 V

32

AO2

Resulting swivel angle command value for master/slave operation

32

REF+

+10 V

Row z

Row f

Pin

Signal

Description

Pin

Signal

Description

2

MA+

Solenoid A+

2

DO7

Rectangular signal 32 Hz

4

MA-

Solenoid A-

4

n. c.

not assigned

6

MB+

Solenoid B+

6

n. c.

not assigned

8

MB-

Solenoid B-

8

AI7+

Power command value

10

Shield

Shield

10

AI7-

Power command value, reference

12

L1O-

Position transducer of valve, feed -, pin 2

12

n. c.

not assigned

14

L1I-

Position transducer of valve, actual value –, pin 4

14

n. c.

not assigned

16

L1I+

Position transducer of valve, actual value +, pin 3

16

n. c.

not assigned

18

L1O+

Position transducer of valve, feed +, pin 1

18

n. c.

not assigned

20

System earth

System earth

20

L2O-

Swivel angle sensor of pump, actual value –, pin 4

22

DO3

Power limitation active

22

L2I-

Swivel angle sensor of pump, actual value +, pin 3

24

DO4

Slave mode active

24

L2I+

Swivel angle sensor of pump, feed –, pin 2

26

DO5

|αcommand – αactual| < window

26

L2O+

Swivel angle sensor of pump, feed +, pin 1

28

DO6

|pcommand – pactual| < window

28

n. c.

not assigned

30

UB

Operating voltage

30

n. c.

not assigned

32

L0

Ground 0 V

32

n. c.

not assigned

Pin assignment of the RS 232 socket

technical illustration-R901089559-Control electronics for adjustment of axial piston pumps A4VS…HS4 (NG40 to NG1000) and A2V…EO4 (NG500 to NG1000) Pressure controller with subordinate swivel angle controller Parameterizable power limitation Leakage compensation Master/slave capability Mooring capability PROFIBUS (optional)

Pin assignment of the PROFIBUS socket

technical illustration-R901089559-Control electronics for adjustment of axial piston pumps A4VS…HS4 (NG40 to NG1000) and A2V…EO4 (NG500 to NG1000) Pressure controller with subordinate swivel angle controller Parameterizable power limitation Leakage compensation Master/slave capability Mooring capability PROFIBUS (optional)

Dimensions in mm

technical illustration-R901089559-Control electronics for adjustment of axial piston pumps A4VS…HS4 (NG40 to NG1000) and A2V…EO4 (NG500 to NG1000) Pressure controller with subordinate swivel angle controller Parameterizable power limitation Leakage compensation Master/slave capability Mooring capability PROFIBUS (optional)

Dimensions in mm

technical illustration-R901089559-Control electronics for adjustment of axial piston pumps A4VS…HS4 (NG40 to NG1000) and A2V…EO4 (NG500 to NG1000) Pressure controller with subordinate swivel angle controller Parameterizable power limitation Leakage compensation Master/slave capability Mooring capability PROFIBUS (optional)

The control electronics may only be unplugged and plugged when de-energized!

Only carry out measurements at the card using instruments with Ri > 100 kΩ.

For switching analog command values and digital call-ups, use relays with gold-plated contacts (low voltages, low currents).

Always shield command and actual value cables; connect shielding to system earth on the card-side, open at one side.

Up to a length of 50 m, use the line type LiYCY 1.5 mm2 for the solenoid conductor. For the position transducer line, use cable type LiYCY 0.5 mm2, shielded. For greater lengths, please contact us.

The distance to aerial lines or radios must be at least 1 m.

Do not lay solenoid conductors and signal lines near power lines.

Commissioning and programming of the control electronics are

described in detail in the operating instructions 30028-B.

For perfect control results, the quality of the sensor technology is important.

PC system requirements:
Windows XP, Windows Vista, Windows 7, RAM (256 MB recommended), 250 MB free hard disk capacity